Cleaver Brooks CBLE-200-700-150

The Cleaver Brooks CBLE model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. The CBLE is a four-pass dry-back firetube boiler, constructed to ASME Section I code and utilizing 5 sq ft of surface area per boiler horsepower. The LE identifier means that this boiler is designed and built to operate with low emissions while maintaining the high fuel to steam efficiency that Cleaver Brooks boilers are known for.

This boiler was purchased by Powerhouse from a customer who was replacing these boilers with new ones. This boiler has since been fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

Brand

Cleaver Brooks

Boiler Type

Firetube

Output Capacity

2,415 - 24150 PPH
Max Pressure 50 - 150 PSIG
Fuel(s) #2 Oil, Natural Gas
Service Saturated Steam
Emission Rating 20 ppm

Need a quote?

TECHNICAL SPECIFICATIONS

GENERAL DESIGN CAPACITIES & INPUTS BURNER & ELECTRICAL DIMENSIONS & WEIGHTS
MANUFACTURER (OEM) CLEAVER-BROOKS OUTPUT CAPACITY 24,150 LBS/HR BURNER MANUFACTURER (OEM) CLEAVER-BROOKS OVERALL LENGTH 25' 5-5/8"
YEAR 1998

HORSEPOWER

700 BHP
MODEL
LE OVERALL HEIGHT 11' 2"
SERIAL NO. OL097980 DESIGN PRESSURE (MAWP) 150 PSIG TYPE FULL MODULATION OVERALL WIDTH
9' 7"
NATIONAL BOARD NO. 9460 OPERATING RANGE 50-140 PSIG FLUE GAS RECIRCULATION (FGR) YES, 18% SHIPPING WEIGHT 52,050 LBS
CRN NO. TBD HEATING SURFACE 3,500 FT² ELECTRIC 460V/3PH/60HZ OPERATING WEIGHT 75,050 LBS
MODEL CB-200-700-150 MAX. FUEL INPUT NG: 28,576,200 BTU/HR #2: 204.1 GPH ATOMIZATION AIR BOILER OUTLET 8" Ø 300# FLG.
ASME CODE SECTION - STANDARD FUELS NATURAL GAS & #2 FUEL OIL CONTROL TYPE SINGLE POINT POSITIONING EXHAUST OUTLET 24" Ø OD
TYPE SCOTCH ADDITIONAL FUELS #6 FUEL OIL BOILER CONTROL SYSTEM -    
DESIGN FOUR-PASS DRY BACK FIRETUBE INPUT GAS PRESSURE MIN: 2.24 PSIG BURNER MANAGEMENT SYSTEM HONEYWELL RM7800    
MOUNTING SADDLES & SKID-MOUNTED TURNDOWN RATIO NG: 10:1 #2: 8:1 FLAME SAFEGUARD IR SCANNER  

INTERNAL CORRUGATED FURNACE & STRAIGHT TUBES EMISSION RATING (NOX) NG: 20 PPM #2: 90 PPM BLOWER MOTOR 75 HP    
    EMISSION RATING (NOX) #2 - BURNER INSTALLED YES    
        PILOT TYPE YES / SPARK    
        INSTRUMENT AIR -    
        AIR COMPRESSOR INCLUDED (7.5 HP)