Cleaver Brooks CBLE-200-246-250

The Cleaver Brooks CBLE model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. The CBLE is a four-pass dry-back firetube boiler, constructed to ASME Section I code and utilizing 5 sq ft of surface area per boiler horsepower. The LE identifier means that this boiler is designed and built to operate with low emissions while maintaining the high fuel to steam efficiency that Cleaver Brooks boilers are known for.

This boiler was purchased brand new from Cleaver Brooks in 2011 and served in our rental fleet. It has since been removed from it's rental stage, and is ready to be fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler will be 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

Brand

Cleaver Brooks

Boiler Type

Firetube

Output Capacity

863 - 8,625 PPH
Max Pressure 15 - 235 PSIG
Fuel(s) #2 Oil, Natural Gas, Propane
Service Saturated Steam
Emission Rating 60 ppm

Need a quote?

TECHNICAL SPECIFICATIONS

GENERAL DESIGN CAPACITIES & INPUTS BURNER & ELECTRICAL DIMENSIONS & WEIGHTS
MANUFACTURER (OEM) CLEAVER-BROOKS OUTPUT CAPACITY 8,625 LB/HR BURNER MANUFACTURER (OEM) CLEAVER-BROOKS OVERALL LENGTH 19' 0-1/2"
YEAR 2011

HORSEPOWER

250 BHP
MODEL
INTEGRAL - LE OVERALL HEIGHT 7' 2"
SERIAL NO. T2659-1-1 DESIGN PRESSURE (MAWP) 250 PSIG TYPE FULL MODULATION OVERALL WIDTH
7' 6-1/2"
NATIONAL BOARD NO. 17470 OPERATING RANGE 15 - 235 PSIG FLUE GAS RECIRCULATION (FGR) YES SHIPPING WEIGHT 18,500 LBS
CRN NO. M4489.5 HEATING SURFACE 1,000 FT² ELECTRIC 480V/3PH/60HZ OPERATING WEIGHT 27,125 LBS
MODEL CBLE-200-246-250 MAX. FUEL INPUT NG: 9,900,000 BTU/HR #2: 71.7 GAL/HR ATOMIZATION AIR BOILER OUTLET 6" Ø 300# STUDDERY FLG.
ASME CODE SECTION - STANDARD FUELS NATURAL GAS & #2 FUEL OIL CONTROL TYPE SINGLE-POINT POSITIONING EXHAUST OUTLET 16" Ø OD
TYPE SCOTCH ADDITIONAL FUELS # 6FUEL OIL BOILER CONTROL SYSTEM -    
DESIGN FOUR-PASS DRYBACK FIRETUBE INPUT GAS PRESSURE MAX: 1.5 PSIG MIN: 1.0 PSIG BURNER MANAGEMENT SYSTEM HONEYWELL RM7800L    
MOUNTING SADDLES & SKID-MOUNTED TURNDOWN RATIO NG: 10:1 #2: 8:1 FLAME SAFEGUARD IR SCANNER  

INTERNAL PLAIN FURNACE & STRAIGHT TUBES EMISSION RATING (NOX) NG: 60 PPM #2: 90 PPM BLOWER MOTOR 20 HP    
    EMISSION RATING (NOX) #2 - BURNER INSTALLED YES    
        PILOT TYPE PROPANE (LPG), NG, SPARK    
        INSTRUMENT AIR OIL ATOMIZATION    
        AIR COMPRESSOR 3 HP (INCLUDED)