Cleaver Brooks CBE-200-100-125

The Cleaver Brooks CBE model is a skid-mounted packaged boiler complete with the boiler, burner, and all required controls and safety equipment. This CB is a three-pass dry-back firetube boiler, constructed to ASME Section IV code and utilizing 5 sq ft of surface area per boiler horsepower.

This boiler was purchased by Powerhouse from a customer who was replacing these boilers with new ones. This boiler has since been fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

Brand

Cleaver Brooks

Boiler Type

Firetube

Output Capacity

1,865 - 3,450 PPH
Max Pressure 0 - 125 PSIG
Fuel(s) #2 Oil, Natural Gas
Service Hydronic Hot Water
Emission Rating Uncontrolled

Need a quote?

TECHNICAL SPECIFICATIONS

GENERAL DESIGN CAPACITIES & INPUTS BURNER & ELECTRICAL DIMENSIONS & WEIGHTS
MANUFACTURER (OEM) CLEAVER-BROOKS OUTPUT CAPACITY 3,450 LB/HR BURNER MANUFACTURER (OEM) CLEAVER-BROOKS OVERALL LENGTH 19' 11"
YEAR 1998

HORSEPOWER

100 BHP
MODEL
PROFIRE OVERALL HEIGHT 6' 11"
SERIAL NO. L-98520 DESIGN PRESSURE (MAWP) 125 PSIG TYPE FULL MODULATION OVERALL WIDTH
5' 11"
NATIONAL BOARD NO. 3676 OPERATING RANGE 0-125 PSIG FLUE GAS RECIRCULATION (FGR) NO SHIPPING WEIGHT 9,820 LBS
CRN NO. - HEATING SURFACE 500 FT² ELECTRIC 480V/3PH/60HZ OPERATING WEIGHT 17,275 LBS
MODEL
CBE-200-100-125
MAX. FUEL INPUT NG: 4,185,000 BTU/HR #2: 30 GAL/HR ATOMIZATION PRESSURE BOILER OUTLET 4" 300# HWS & HWR
ASME CODE SECTION - MAX. FUEL INPUT #2 - CONTROL TYPE SINGLE-POINT POSITIONING EXHAUST OUTLET 12" Ø OD
TYPE SCOTCH STANDARD FUELS NATURAL GAS & #2 FUEL OIL BOILER CONTROL SYSTEM -    
DESIGN THREE PASS DRYBACK FIRETUBE INPUT GAS PRESSURE MAX: 6.7 " WC MIN: 1.7 " WC BURNER MANAGEMENT SYSTEM CB110    
MOUNTING LEGS & SKID-MOUNTED TURNDOWN RATIO NG: 1.85:1 #2: 1.85:1 FLAME SAFEGUARD UV SCANNER  

INTERNAL STRAIGHT FURNACE & TUBES EMISSION RATING (NOX) UNCONTROLLED BLOWER MOTOR 2 HP    
    EMISSION RATING (NOX) #2 - BURNER INSTALLED YES    
        PILOT TYPE NATURAL GAS    
        INSTRUMENT AIR -    
        AIR COMPRESSOR -